Configuring Switches
The Switches tab contains settings to configure the auxiliary input switch for the KNX gateway.
|
Standard properties are shown in bold. Advanced properties are shown in italics. Displayed fields can be sorted in one of two ways by clicking the following icons: Initially only the basic fields are shown. To reveal all fields, click the button. |
Properties
Functions
The DDNG-KNX auxiliary input switch can be configured to perform one of the following functions for the specified Logical Area and Channel:
|
|
|
The input switch functions can be used in DyNet and/or mapped to KNX. The available parameters differ for each type of function selected. The descriptions below assume that the input is connected to a button.
Advanced
-
Sign On - This diagnostic function checks the button by sending a DyNet sign-on message to the network.
-
Event Control - Remotely triggers an event on a different device on the network.
-
Panic - Activates or deactivates the Panic preset.
-
Panel Enable/Disable
-
Set Join Level - Dynamically modifies the native join of UIs/sensors in an area. The Logical Address > Area/Join properties determine which devices in which area are affected.
-
DyNet 1 Logical Message - This advanced function sends a customised DyNet logical message over the network.
We strongly recommend consulting with Dynalite before attempting to use this. -
DyNet 1 Physical Message - This advanced function sends a customised DyNet physical message over the network.
We strongly recommend consulting with Dynalite before attempting to use this.
| Property | Description |
|---|---|
Panic |
If True, sets the selected area to panic mode when the button is pressed, raising all dimming levels to 100% and locking UI controls for that area. |
Control type |
Enable, Disable, or Trigger an event when the button is pressed. |
Device Code |
Identifies the target device type. |
Box number |
Identifies the target device. |
Event number |
Identifies the event on the target device. |
Enable Panel |
Enables (True) or disables (False) the input. |
Fade time |
The time taken for dimming levels to fade from their current setting to 100%. |
DyNet mute |
Stop DyNet messages being created by this function. |
Channel level
Set a logical channel to a specified percentage output.
-
Channel Level
-
Increment Channel Level Step
-
Decrement Channel Level Step
| Property | Description |
|---|---|
Level (%) |
Specified percentage |
Start level |
(Increment/Decrement) Sets the starting light level on the channel (0-254) |
End level |
(Increment/Decrement) Sets the ending light level on the channel (0-254) |
Step |
(Increment/Decrement) The step size for each increment (default: 5) |
Fade (rounded to 10 ms) |
Fade time in milliseconds (default 2s). |
Off preset |
Defines the off preset number for the area. |
DyNet mute |
Stop DyNet messages being sent over the network (True/False). |
Custom
Select from any of the available actions in the Action Chain Editor:
| Property | Description |
|---|---|
Press actions |
Selects the actions to execute on each type of button event. |
Release actions |
|
Extended press actions |
|
Extended release actions |
Available Actions
|
Advanced >
|
Room Status
Hospitality applications only, see Multiroom System Manager.
One Touch
-
Toggle Preset - Fades between the On Preset and Off Preset
-
One touch with ramp - Short press activates Toggle Preset. Extended press alternates between ramping up or down.
-
One touch ramp with program - When the button is released after ramping, the new level is saved to the On Preset.
-
Single direction one touch - Short press recalls the Preset. Extended press ramps toward the target Level (%).
| Property | Description |
|---|---|
Preset / On Preset |
Defines the preset for the button’s ON state. |
Off Preset |
Defines the preset for the button’s OFF state. |
Fade (rounded to 10 ms) |
Time taken to reach the preset level if the button is tapped. |
Ramp rate (rounded to 10 ms) |
Time taken to ramp up to the required level if the button is held. |
Min ramp level (%) |
Minimum light level when ramping down. |
Level (%) |
(Single direction one touch) Defines the channel level to ramp towards when the button is held. |
DyNet Mute |
Stops DyNet messages being created by this function. |
Double send stop fade |
If True, 'stop fade' command is sent twice to compensate for busy networks. |
Preset
-
Preset - Recall a preset over DyNet
-
Off Preset - Instantly drops all channels in the specified area to 0% with no fade time.
-
Reset Preset - Resets all channels in an area to the currently selected preset, overriding any individual channel level changes that were made since the preset was selected.
-
Preset Offset - Increments all other preset commands by this amount.
-
Preset with program - If button is tapped this preset is recalled. If button is held down for three seconds, this preset is overwritten with the current channel levels.
-
Increment Multi-preset - Each button press increments the preset number up through this range, then loops back. If the current preset is out of range, the first press recalls the Start Preset.
| The End Preset must be greater than the Start Preset. |
-
Decrement Multi-preset - Each button press decrements the preset number down through this range, then loops back. If the current preset is out of range, the first press will recall the Start Preset.
| The End Preset must be lower than the Start Preset. |
| Property | Description |
|---|---|
Preset |
Defines the preset for the button’s ON state. |
Off Preset |
Defines the area’s OFF preset for the button’s indicator LED. |
Preset offset |
When button is pressed, all other preset commands are incremented by this amount. |
Start Preset |
Each button press increments/decrements the preset number through this range, then loops back. If the current preset is out of range, the first press recalls the Start Preset. |
End Preset |
|
Fade (rounded to 10 ms) |
Time taken to reach the ON state. |
DyNet Mute |
Stops DyNet messages being created by this function. |
Ramp
Pressing and holding a button gradually increases/decreases the channel level. Releasing the button stops the channel at the present level.
-
Ramp up channel level
-
Ramp down channel level
| Property | Description |
|---|---|
Min ramp level (%) |
Minimum light level when ramping down. |
Fade (rounded to 10 ms) |
Time taken to ramp from the current level up to 100% or down to Min ramp level (%). |
On channels only |
If True, only channels with a level 1% or higher will ramp. |
DyNet Mute |
Stops DyNet messages being created by this function. |
Double send stop fade |
If True, the 'stop fade' command is sent twice to ensure correct operation. |
Task
Control a task stored locally on the device or remotely on another device.
-
Run local task
-
Run remote task
| Property | Description |
|---|---|
Control type |
Start, Pause, or Stop the selected task. |
Device code |
Identifies the target device type. |
Box number |
Identifies the target device address. |
Task |
Specifies the task number on the target device. |