BACnet Gateway

To enable BACnet integration, the PDDEG-S can be configured as a BACnet gateway. A BACnet gateway provides configurable data points allowing bi-directional communication to Dynalite’s powerful distributed network architecture from a BACnet based building management system (BMS). Only BACnet over Ethernet with a UDP connection is supported.

BACnet point objects
No. Function Object type Data Type Read/ Write Point description

1

Total Offline Devices

Job, Floor

Analog

R

Count of any offline devices for a Job or Floor.[1]

2

Total Driver and Lamp Faults

Job, Floor, Area

Analog

R

Count of any offline drivers or lamps for a Job, Floor or Area.

3

Offline Device Alarm

Job, Floor

Binary

R

Indicator of any offline devices for a Job or Floor.[1]

4

Driver or Lamp Fault Alarm

Job, Floor, Area

Binary

R

Indicator of any offline drivers or lamps for a Job, Floor or Area.

5

System Manager Offline Device Alarm

SM

Binary

R

Indicator that System Manager has identified one or more offline devices.[1]

6

System Manager Driver or Lamp Fault Alarm

SM

Binary

R

Indicator that System Manager has identified one or more driver or lamp failures.

7

Preset

Area

Analog

R/W

Read and write the preset number for an Area.

8

Current Temperature

Area

Analog

R

Read the current Temperature (Celsius) for an Area.

9

Temperature Setpoint

Area

Analog

R/W

Read and write the temperature setpoint for an Area.

10

Channel Level

Channel

Analog

R/W

Read and write the level of a single channel within an Area.

11

Driver Status

Driver

Binary

R

Read if a single driver in a fixture is online or offline.

12

Lamp Status

Driver

Binary

R

Read if a single lamp in a fixture is working or not working.

13

Channel Runtime

Driver

Analog

R

Circuit/driver usage in minutes.

14

Device Offline Status

Device

Binary

R

Read if a single device in the system is online or offline.[1]

15

Light Level (Lux)

Device

Analog

R

Read the LUX level from a single DyNet Sensor.[1]

It is not essential to have floor plans in your job to configure BACnet integration.

1. Not currently available for DALI devices (sensors and dry contact interfaces)