Device Properties
Standard properties are shown in bold. Advanced properties are shown in bold italics. Initially only the basic fields are shown. Most standard setups do not require advanced properties, but you can reveal all fields by clicking the button.Displayed fields can be sorted in one of two ways by clicking the following icons: Refer to the property description pane at the bottom of the editor for explanations of each property. |
The Device Properties editor includes the following categories for information about the device and basic configuration:
Device Identification
Property | Description |
---|---|
Device Name |
Used to identify the device. |
Location |
The physical location of the device. |
Description |
Other identifying information for the device. |
Box number |
Physical address used for identification by the Dynalite system. |
Serial number |
The serial number of the device. |
Device location sequence |
Identifies devices sequentially on a series network, not required. |
System designer device number |
Not required. |
IPv4 Address |
32-bit network address expressed in decimal |
IPv6 Address |
128-bit network address expressed in hexadecimal (32 hexadecimal numbers) |
Product Information
Property | Description |
---|---|
Product name |
These fields are populated automatically. |
Has RTC |
Device has a built-in real-time clock. Leave set to True. |
Device Status
Property | Description |
---|---|
Device status list |
These fields are populated automatically. |
Start-up Settings
Property | Description |
---|---|
Metric polling startup delay (sec) |
If Enabled, the device sends a sign-on DyNet message when turned on or reset. |
Start delay (rounded to 10 ms) |
Delay after start-up before sending sign-on message (maximum: 00:30:000). |
Real-Time Clock
Property | Description |
---|---|
Broadcast time |
Enable or disable the real-time clock’s time reporting. |
Broadcast date |
Enable or disable the real-time clock’s date reporting. |
Broadcast interval (seconds) |
The real-time clock reporting interval 1-65534 seconds. The default is 10 minutes. |
Network Time Protocol (NTP) |
Enabled or Disabled. |
NTP Polling Interval (days) |
Default 30, maximum 366. |
NTP IP Address / Hostname |
The server to poll for NTP updates. |
Ethernet Applications
The PDTS does not currently support remote web server access. These properties should be left to their default settings unless instructed by Dynalite support. |
Property | Description |
---|---|
Web server |
Enabled or Disabled. |
Secure connection (HTTP/HTTPS) |
HTTPS only. |
Authentication required for |
Specifies when web service authentication is required:
|
Starting web page |
The default UI uses index.htm. |
Web server caching |
Enabled or Disabled. Certain browsers such as Safari may require caching to be disabled to work. |
CGI Timeout (milliseconds) |
Changes the CGI command timeout period |
Anti-CSRF token |
Enabled or Disabled |
Scheduler
Property | Description |
---|---|
Event schedule |
Enable or Disable all schedules. |
Reserved event schedule records |
The number of reserved schedule records. |
Reserved task length (bytes) |
Default minimum reserved length of task list. |
Grace Period (minutes) |
Task grace period. |
Reserved event schedule name (bytes) |
Reserved bytes for UTF-8 text title. |
Reserved special event records |
The number of reserved special event records. |
Reserved special event name (bytes) |
Reserved bytes for UTF-8 text title. |
Reserved public holiday records |
The number of reserved public holiday records. |
Reserved public holiday name (bytes) |
Reserved bytes for UTF-8 text title. |
Panel Data
Property | Description |
---|---|
Locale |
Select the onscreen keyboard language:
|
Project Settings
Property | Description |
---|---|
UI Creator project path |
The location (on the SB machine) of the UI Creator project folder for this device. |
Temperature Sensor
Property | Description |
---|---|
Control |
Enable/disable temperature sensor |
Broadcast temperature |
If enabled, the device periodically broadcasts temperature to the network. |
Respond to temperature requests |
Enable/disable sending of temperature status from this device. |
Measured temperature offset (°C) |
Adjusts the broadcast temperature by the positive or negative figure defined here. |
Min trigger time |
The time the sensor must wait between each broadcast, even if temperature change is greater than Delta Value. This is to prevent frequent broadcast of temperature over the network. |
Max trigger time |
The maximum time between broadcasts, even if the temperature change is less the defined Delta Value. |
Delta value (°C) |
If the temperature changes by more than the defined value, AND the Min trigger time has elapsed, the current temperature will be broadcast. |
Logical Area |
Logical Area where the device is located |
BLA |
The base link area, if any, where the device is located. Can be set to Disabled if not applicable. |
Logical Channel |
The logical channel the device is assigned to. |
Join |
The static join of the device |
Humidity Sensor
Property | Description |
---|---|
Control |
Enable/disable humidity sensor |
Broadcast humidity |
If enabled, the device periodically broadcasts humidity to the network. |
Respond to humidity requests |
Enable/disable sending of humidity status from this device. |
Measured humidity offset (%) |
Adjusts the broadcast humidity by the positive or negative figure defined here (default: 5). |
Min trigger time |
The time the sensor must wait between each broadcast, even if humidity change is greater than Delta Value. This is to prevent frequent broadcast of temperature over the network. |
Max trigger time |
The maximum time between broadcasts, even if the humidity change is less the defined Delta Value. |
Delta value (°C) |
If the humidity changes by more than the defined value, AND the Min trigger time has elapsed, the current humidity will be broadcast. |
Logical Area |
Logical area where the device is located |
BLA |
The base link area, if any, where the device is located. Can be set to Disabled if not applicable. |
Logical Channel |
The logical channel the device is assigned to. |
Join |
The static join of the device |