BACnet Editor

This editor contains generic BACnet settings. Please ensure General > BACnet service is enabled.

Port, Network ID, and Device ID can stay on default settings, or click the sb icon advanced  Advanced button to change these values.

Every BACnet device must have a unique Device ID within the BACnet network. Both Device ID and Network ID are provided by the BACnet administrator. The default BACnet port is 47808 (0xBAC0) but may be changed if required.

If you have previously run the BACnet Wizard and defined your BACnet points, you can click sb icon export csv Export CSV and sb icon import csv Import CSV to save/load them to/from a spreadsheet.
sb bacnet editor
The PDDEG-S must be rebooted for changes to take effect. A reset is not sufficient.