Test Functionality

The final step before handover to the BMS contractor is to check that each point is functioning correctly.

Using a BACnet client, test each point by: * Setting a data point value from the BACnet client and monitoring the message in the SB Network Log (writing). * Setting a data point value from SB and monitoring the corresponding data point value in the BACnet client (reading).

The System Builder Virtual Panel and sb icon dynet packet sender DyNet Packet Sender enable you to send out the DyNet messages that (if mapped to BACnet) are read by the BACnet client. Click the sb icon configure virtual panel Configure icon or press Alt+F9 to ensure the virtual panel is configured to the area selected in Areas View.

sb virtual panel
For more information refer to the PDDEG-S BACnet Integration Application Note, available from https://www.dynalite.com/support.