OPC UA Dataset

The SM OPC UA Server uses the following dataset to communicate with the BMS

Name Data type Range Description

Areas

Current Preset No

UInt16

0 – 65,000
(typically 1 – 16)

Preset scene number in an area

Current Temperature

Float

-127 – 127°C
(0.25°C steps)

The current temperature reading from a temperature sensor in an area

Metered Power

Float

User specified

Realtime power Modbus meter reading for an area

Motion Timeout

UInt16

0 – 1092 minutes
(18 h:12 m)

The sensor occupancy timeout setting in an area

Notional Power

Float

User specified

Realtime calculated power reading for an area

Setpoint Temperature

Float

-127 – 127°C
(0.25°C steps)

The temperature setpoint in an area

Total Offline Devices

UInt16

0 – 65,534

Total number of devices in an area that are currently offline

Total Offline Drivers or Lamps

UInt16

0 – 65,534

Total number of drivers or lamps in an area that are currently offline

DALI Devices

Online Status

Boolean

0/1

Driver is online or offline

DALI Sensors

Lux Level

UInt16

0 – 65,534

The calibrated lux reading from a specific sensor

Devices

Online Status

Boolean

0/1

Device is offline/online

Emergency Test Groups [Group Name]

Total Duration Test Failure

UInt16

0 – 65,534

The number of drivers that failed the last duration test

Total Duration Test Running

UInt16

0 – 65,534

The number of drivers running the duration test

Total Duration Test Success

UInt16

0 – 65,534

The number of drivers that passed the last duration test

Total Functional Test Failure

UInt16

0 – 65,534

The number of drivers that failed the last Functional test

Total Functional Test Running

UInt16

0 – 65,534

The number of drivers running the Functional test

Total Functional Test Success

UInt16

0 – 65,534

The number of drivers that passed the last Functional test

Total Emergency Drivers

UInt16

0 – 65,534

The number of drivers in the group

General System Health

DyNet Connection Status

Boolean

0/1

System Manager cannot connect to any gateway

Total Offline Drivers

UInt16

0 – 65,534

Total number of drivers in the job that are currently offline

Total Offline Devices

UInt16

0 – 65,534

Total number of devices in the job that are currently offline

Total Offline Lamps

UInt16

0 – 65,534

Total number of lamps in the job that are currently offline

Total Trunk Gateways

UInt16

0 – 65,534

Total number of gateways in the job

Total Offline Trunk Gateways

UInt16

0 – 65,534

Total number of gateways in the job that are currently offline

Load Control Channels

Channel Runtime

UInt24

0 - 16,777,215

Lamp usage in minutes

Driver Status

Boolean

0/1

Driver is offline/online

Lamp Status

Boolean

0/1

Lamp is offline/online

Logical Channels

Logical Channel Level

UInt16

0 – 100

Percentage level of a single channel within an area

Sensors

Lux Level

UInt16

0 – 65,534

The calibrated lux reading from a specific sensor