OPC UA Dataset
The SM OPC UA Server uses the following dataset to communicate with the BMS
Name | Data type | Range | Description |
---|---|---|---|
Areas |
|||
Current Preset No |
UInt16 |
0 – 65,000 |
Preset scene number in an area |
Current Temperature |
Float |
-127 – 127°C |
The current temperature reading from a temperature sensor in an area |
Metered Power |
Float |
User specified |
Realtime power Modbus meter reading for an area |
Motion Timeout |
UInt16 |
0 – 1092 minutes |
The sensor occupancy timeout setting in an area |
Notional Power |
Float |
User specified |
Realtime calculated power reading for an area |
Setpoint Temperature |
Float |
-127 – 127°C |
The temperature setpoint in an area |
Total Offline Devices |
UInt16 |
0 – 65,534 |
Total number of devices in an area that are currently offline |
Total Offline Drivers or Lamps |
UInt16 |
0 – 65,534 |
Total number of drivers or lamps in an area that are currently offline |
DALI Devices |
|||
Online Status |
Boolean |
0/1 |
Driver is online or offline |
DALI Sensors |
|||
Lux Level |
UInt16 |
0 – 65,534 |
The calibrated lux reading from a specific sensor |
Devices |
|||
Online Status |
Boolean |
0/1 |
Device is offline/online |
Emergency Test Groups [Group Name] |
|||
Total Duration Test Failure |
UInt16 |
0 – 65,534 |
The number of drivers that failed the last duration test |
Total Duration Test Running |
UInt16 |
0 – 65,534 |
The number of drivers running the duration test |
Total Duration Test Success |
UInt16 |
0 – 65,534 |
The number of drivers that passed the last duration test |
Total Functional Test Failure |
UInt16 |
0 – 65,534 |
The number of drivers that failed the last Functional test |
Total Functional Test Running |
UInt16 |
0 – 65,534 |
The number of drivers running the Functional test |
Total Functional Test Success |
UInt16 |
0 – 65,534 |
The number of drivers that passed the last Functional test |
Total Emergency Drivers |
UInt16 |
0 – 65,534 |
The number of drivers in the group |
General System Health |
|||
DyNet Connection Status |
Boolean |
0/1 |
System Manager cannot connect to any gateway |
Total Offline Drivers |
UInt16 |
0 – 65,534 |
Total number of drivers in the job that are currently offline |
Total Offline Devices |
UInt16 |
0 – 65,534 |
Total number of devices in the job that are currently offline |
Total Offline Lamps |
UInt16 |
0 – 65,534 |
Total number of lamps in the job that are currently offline |
Total Trunk Gateways |
UInt16 |
0 – 65,534 |
Total number of gateways in the job |
Total Offline Trunk Gateways |
UInt16 |
0 – 65,534 |
Total number of gateways in the job that are currently offline |
Load Control Channels |
|||
Channel Runtime |
UInt24 |
0 - 16,777,215 |
Lamp usage in minutes |
Driver Status |
Boolean |
0/1 |
Driver is offline/online |
Lamp Status |
Boolean |
0/1 |
Lamp is offline/online |
Logical Channels |
|||
Logical Channel Level |
UInt16 |
0 – 100 |
Percentage level of a single channel within an area |
Sensors |
|||
Lux Level |
UInt16 |
0 – 65,534 |
The calibrated lux reading from a specific sensor |