OPC UA Objects

OPC UA stores configuration data in objects. The table below shows the configuration data that SM can map to OPC UA objects.

Object properties Data Points Methods Alarms

Areas

  • Data Point

  • Area Name

  • Area No

Current Preset No
Current Temperature
Metered Power
Motion Timeout
Notional Power

SetAreaPreset
SetAreaTemperature
SetAreaTemperatureUpDown

Devices

  • Data Point

  • Box Number

  • Device Code

Online Status

DeviceStatusAlarm

Emergency Test Groups [Group Name]

  • Data Point

  • Emergency Group ID

Total Duration Test Failure
Total Duration Test Running
Total Duration Test Success
Total Functional Test Failure
Total Functional Test Running
Total Functional Test Success
Total Emergency Drivers

General System Health

  • Data Point

DyNet Connection Status
Total Offline Drivers
Total Offline Devices
Total Offline Lamps
Total Offline Trunk Gateways
Total Trunk Gateways

DyNetConnectionOfflineAlarm

Load Control Channels

  • Data Point

  • Box Number

  • Channel Name

  • Channel No

  • Device Code

  • Device UID

Driver Status
Channel Runtime
Lamp Status

DriverOfflineAlarm
-
LampOfflineAlarm

Logical Channels

  • Data Point

  • Area No

  • Channel Name

  • Channel No

Channel Level

SetLogicalChannelLevel

Sensors

  • Data Point

  • Box Number

  • Device Code

  • Device Location

  • Device Name

  • Product Name

LUX Level